5.3.2.1.3.3. SERIAL PORT TRANSMISSION PARAMETERS
For proper operation of ADA-13040MG with device connected to his RS485/RS422 serial port, should be set the same transmission
parameters for both devices.
Select Basic Serial Settings and enter Baud Rate, Data Bits, Parity, Stop Bits, the same parameter like has device connected to
the serial port of the converter.
5.3.2.1.4. SERIAL BRIDGE PROFILE CONFIGURATION
Choosing the Serial Bridge profile enable direct communication between two devices connected to two ADA-13040MG converters
over the network as if they were connected with a serial cable. A properly configured ADA-13040MG will start automatically
communication with each other. Press [Apply] for save the configuration
After saving the Serial Bridge profile, will open section Serial Bridge Settings (fig.21) with operating parameters like on picture below.
Select Initiate serial bridge to the following device option and enter IP address and 2101 Port of ADA-13040MG with which to
create the serial bridge over the network. Additionally can be selected [Enable TCP Keep-Alive] option which keeps connection even
if the data is not transmitted. Select Allow other devices to initiate serial bridge and enter 2101 port on which other the converter
will automatically start communication and can be set also [Enable TCP Keep-Alive] option which keeps connection even if the data
is not transmitted.
Fig. 21. Example configuration of TCP Serial Bridge
ATTENTION !
Default port of serial port service is 2101.
If on the local network is conflict with other network service using the same port, in the converter's port configuration
change number of port into another for the server and client service.
5.3.2.1.4.1. SERIAL PORT TRANSMISSION PARAMETERS
For proper operation of ADA-13040MG with device connected to his RS485/RS422 serial port, should be set the same transmission
parameters for both devices.
Select Basic Serial Settings and enter Baud Rate, Data Bits, Parity, Stop Bits, the same parameter like has device connected to
the serial port of the converter.
5.3.2.1.5. INDUSTRIAL AUTOMATION (MODBUS GATEWAY) CONFIGURATION
Choosing the Industrial Automation (Modbus Gateway, Fig.16) profile, will be possible to configure ADA-13040MG for
communication by the use of MODBUS-RTU master/slave or MODBUS-ASCII master/slave protocol. The converter converts frames
of MODBUS-RTU/ASCII protocol to MODBUS-TCP and send via WLAN/LAN/WAN to devices with MODBUS-TCP protocol or other
servers (ADA-14040, ADA14110, ADA-13040MG, ADA-13110MG) operating in Industrial Automation (MODBUS Gateway) mode
with connected MODBUS-RTU/ASCII devices. Press [Apply] for saving this profile.
5.3.2.1.5.1. CONFIGURATION FOR COMMUNICATION WITH DEVICES MODBUS-
MASTER TYPE
In section Industrial Automation Settings, press [Change Protocol] link. Then in section Select IA Protocol (figure below) select
type of device, connected to serial port of ADA-13040MG, as Serial Master and MODBUS-RTU or MODBUS-ASCII protocol for
communication between connected devices. Press [Apply] for saving configuration.